Box-type air-cooled chiller (1P)
Box-type air-cooled chiller (1P)

Box-type air-cooled chiller (1P)

Model:
CAN-COO15-0001PS
Applied range:
Box-typeair-cooled chiller is the 1 commonly used in industrial, commercial and scientific research in the field of refrigeration equipment, it through the compression cycle of refrigerant, the heat from the inside to the outside, so as to achieve the cooling effect. The equipment is mainly composed of four components: compressor, condenser, expansion valve and evaporator, which work together to complete the refrigeration cycle.
Date issued:
2024-12-23 21:57:58
Equipment Size:
500× 500 × 900 (subject to actual conditions)
Weight:
58kg

Details

This box-type air-cooled chiller (1P), model CAN-COO15-0001PS from Canrd, is developed as a compact cooling solution for temperature-sensitive processes across multiple battery production lines, including prismatic aluminum case, dry electrode preparation, solid-state, metal lithium, cylindrical, zinc-ion, and pouch cell setups. Its air-cooled design eliminates the need for external water circulation, simplifying installation in lab or pilot-scale environments where consistent heat removal is essential for electrode drying, electrolyte filling, or cell testing. While specific cooling capacity is not detailed here, the 1P (1-horsepower) rating indicates suitability for moderate thermal loads typical of small-to-medium R&D equipment. The chiller’s robust construction supports reliable long-term operation under continuous duty cycles, helping maintain process stability. Common applications include temperature regulation for calendering, coating, or solvent recovery units, making it a versatile auxiliary component for advanced battery material and cell fabrication research.
nominal refrigerating capacity
2.5kw/h
control temperature
8-30 ℃
equipment weight
58kg
power
0.87kw
equipment size
500 × 500 × 900 (subject to actual conditions)
power supply
single phase 220V/50Hz
Pump power
0.25kw
controller
fully intelligent temperature control system
temperature control
outlet water temperature sensor
Compressor input power
0.75kw
heat dissipation fan
external rotor axial flow fan
chilled water flow
2.4 m/h
Heat exchange tube material
high-efficiency heat exchange copper tube
exhaust pressure
1.4-2.0MPa
Exhaust mode
Side outlet
water tank capacity
25L
pump flow
0.9 m/h
pump lift
15m
heat dissipation air volume
1580m/h
Water pipe diameter
DN12mm
chilled water pressure drop
40-60kPa
refrigerant charge
1.2KG
number of fans
1
operating current
1.5A
refrigerant model
R22

& nbsp; & nbsp; & nbsp; Box-type air-cooled chiller is 1 kind of refrigeration equipment commonly used in industrial


1. adopt world famous brand compressors as the core power and use international first-class brand accessories;
2