Box air-cooled chiller (2P)
Box air-cooled chiller (2P)

Box air-cooled chiller (2P)

Model:
CAN-COO15-0002PS
Applied range:
Box-typeair-cooled chiller is the 1 commonly used in industrial, commercial and scientific research in the field of refrigeration equipment, it through the compression cycle of refrigerant, the heat from the inside to the outside, so as to achieve the cooling effect. The equipment is mainly composed of four components: compressor, condenser, expansion valve and evaporator, which work together to complete the refrigeration cycle.
Date issued:
2024-12-23 21:57:42
Equipment Size:
700× 650 × 1300 (subject to actual conditions)
Weight:
124kg

Details

This product is designed for thermal management in advanced battery manufacturing environments. The Box air-cooled chiller (2P) from Canrd provides a compact cooling solution suitable for a range of production lines, including prismatic aluminum case, dry electrode preparation, solid-state, metal lithium, cylindrical, zinc-ion, and pouch cell applications. With a nominal cooling capacity of 2 horsepower, it relies on air-cooled heat rejection, making it a stand-alone unit that does not require an external cooling water circuit. Its enclosed, box-type construction integrates the compressor, condenser, and control system, facilitating straightforward installation and maintenance in laboratory or pilot-scale battery assembly setups. While specific temperature stability or flow rate parameters are not detailed, the chiller is intended to maintain consistent process temperatures for electrode coating, electrolyte filling, or cell testing equipment. This unit supports research and production facilities seeking reliable, space-efficient cooling for their battery development workflows.
Control temperature
8-30 ℃
Power supply
Single phase 220V/50Hz
Equipment weight
124kg
Nominal refrigerating capacity
5kw/h
Equipment size
700 × 650 × 1300 (subject to actual conditions)
Power
1.5kw
Pump power
0.375kw
controller
fully intelligent temperature control system
temperature control
outlet temperature sensor
Compressor input power
1.5kw
heat dissipation fan
external rotor axial flow fan
chilled water flow
1.2 m/h
Heat exchange tube material
high-efficiency heat exchange copper tube
exhaust pressure
1.4-2.0MPa
Exhaust mode
Top air
water tank capacity
40L
pump flow
2.0 m/h
pump lift
15m
heat dissipation air volume
3150m/h
Water pipe diameter
DN25mm
chilled water pressure drop
40-60kPa
refrigerant charge
1.2KG
number of fans
1
operating current
3A
refrigerant model
R22

& nbsp; & nbsp; & nbsp; Box-type air-cooled chiller is 1 kind of refrigeration equipment commonly used in industrial


1. adopt world famous brand compressors as the core power and use international first-class brand accessories;
2